Back to top
Specifications
| Performance Specifications |
Accuracy
(linear ranges) |
Liquid |
± 1.0% of flow rate |
| Gas/steam |
± 1.5% of flow rate |
| Analog output |
Add ± 0.1% of full scale |
| Repeatability |
± 0.15% of flow rate |
| Response Time |
Adjustable from 1 to 100 sec (analog output version) |
Back to top
| Operating Specifications |
| Fluid types |
Liquid, gas, or steam |
| Measurable flow velocities |
Liquid |
1.5 to 32 ft/sec (0.5 to 9 m/sec) |
| Gas/steam |
to 300 ft/sec ( to 91 m/sec) (p=density lb/ft³ (kg/m³) |
| Process pressure |
V-Bar-600/60S |
125 psi (8.62 bar) |
| V-Bar-700 |
Up to 2000 psi (138 bar) |
| V-Bar-910/960 |
According to flange rating, up to 900 psi |
| Process temperature limit |
V-Bar-600/60S |
400 °F (204 °C) max |
| V-Bar-700 |
500 °F (260 °C) max |
| V-Bar-910/960 |
400/500 °F (260/260 °C) max |
| Ambient temperature limit |
Standard |
– 20 to 140°F (– 29 to 60°C) |
| Ambient temperature limit |
32 to 140°F (0 to 60°C) |
| Ambient humidity limit |
Up to 100% RH non-condensing |
| Power requirements |
Standard |
18 to 40 VDC, 35 mA max |
| Option |
110/220 VAC |
| Output signals |
Scalable 4 to 20 mA current and scalable frequency/pulse 0 to 10 kHz HART® communication protocol |
Back to top
| Physical Specifications |
| Materials |
Wetted parts |
316L stainless steel or the cast equivalent, CF3M (bronze and carbon steel on V-BAR-600/60S) |
| All other parts |
Aluminum, 316 stainless steel, carbon steel (bronze and carbon steel on V-BAR-600/60S) |
| Electronics enclosure |
383 aluminum; NEMA 4X |
| Process connection |
V-Bar-600/60S |
2" NPT / provided with 2" bronze valve hot tap |
| V-Bar-700 |
2" NPT or 2" 150#, 300#, 600#, or 900# ANSI raised face flange (no hot tap) |
| V-Bar-910/960 |
2" 150#, 300#, 600#, or 900# ANSI raised face flange (hot tap) |
Isolation valve
(V-Bar-600/60S only) |
2" full port bronze gate valve, 125 psi (8.62 bar) max |
| Pressure tap and bleed valve |
Standard 1/4" NPT pipe nipple with 1/4" stainless steel bleed valve (bleed valve is bronze for V-Bar-600/60S only). Provides connections for mounting optional pressure transmitter (Model PT). |
| Model PT pressure transmitter (optional) |
A pressure transmitter can be mounted using the 1/4" NPT connection on the bleed valve supplied with the meter, eliminating the need for a separate pressure tap. A 4-20 mA output, scaled to the desired pressure range, is provided. |
Temperature sensor
(RTD option) |
A 1000 O, 3-wire, platinum RTD can be mounted inside the stem of the meter probe, eliminating the need for a separate temperature tap. |
Temperature transmitter
(TXX option) |
Includes the RTD option with an additional 4 to 20 mA output, scaled to the desired temperature range. |
| Mounting |
Standard |
Transmitter integrally mounted on sensor |
| Option |
Transmitter remote mounted |
| Display |
Local indicator alternates; displays flow rate and totalized flow in user-selectable, engineering units. It is a 2-line, 8-character per line, LCD display. |
| Approvals |
FM |
Class I, Division 2, Groups A, B, C, & D
Class II, III, Division 2, Groups F & G |
| CSA |
Class I, Division 2, Groups A, B, C, & D
Class II, Division 1, Groups F & G
Class III |
Back to top
Installation
| Installation Specifications |
| Tap Size |
1.875" (47.6 mm) minimum diameter |
| Mounting |
Install flow meter vertically, horizontally, or at any angle. The meter is attached perpendicular to the axis of the pipe and should not be mounted "upside-down" (with its top section hanging below the pipe mount). For liquid service, the flow line must be full during flowmeter operation. In vertical lines, flow direction should be upward for optimum flowmeter performance. |
| Straight run piping |
(D = internal diameter of pipe) |
Upstream |
Downstream |
| One 90° elbow before meter |
10 D |
5 D |
| Two 90° elbows before meter |
15 D |
5 D |
| Two 90° elbows out of plane before the meter |
30 D |
5 D |
| Reduction before the meter |
10 D |
5 D |
| Regulator or valve partially closed before the meter |
30 D |
5 D |
| Site selection |
Select installation location to minimize turbulence and swirl. The piping configuration, i.e., valves, elbows, pumps, may add disturbances to the flow. |
| Hot-tap compatibility |
The V-Bar-600/60S is hot-tap compatible, which means that the sensor can be installed and removed under full-flow conditions. The V-Bar-910/960 is hot-tap compatible when installed with a 2" double flanged, full- port ball or gate valve. The V-Bar-700 requires line shutdown and depressurization prior to installation. |
Back to top
Model Codes
| Model Codes |
| Category |
Description |
Suffix Codes |
| Model |
Liquid or gas service, 400°F (204°C) |
600 |
- |
- |
- |
- |
| Steam service, 400°F (204°C) |
600S |
- |
- |
- |
- |
| Liquid, gas, or steam service, 500°F (260°C) |
700 |
- |
- |
- |
- |
| Liquid, gas, or steam service, 400°F (204°C) |
910 |
- |
- |
- |
- |
| Liquid, gas, or steam service, 500°F (260°C) |
960 |
- |
- |
- |
- |
| Connection |
2", male NPT (Model 700, 800, 80S) |
- |
2NPT |
- |
- |
- |
| 2", 150# flange (Model 700, 910, 960) |
- |
2F150 |
- |
- |
- |
| 2", 300# flange (Model 700, 910, 960) |
- |
2F300 |
- |
- |
- |
| 2", 600# flange (Model 700, 910, 960) |
- |
2F600 |
- |
- |
- |
| 2", 900# flange (Model 700, 910, 960) |
- |
2F900 |
- |
- |
- |
| Thread-o-let, xx = 03 to 80" (Models 600/60S) includes 2" isolation valve |
- |
VXX |
- |
- |
- |
| Pressure Transmitter |
No pressure transmitter |
- |
- |
XX |
- |
- |
| PT for pressure range 0 to 50 psig (0 to 3.44 barg) |
- |
- |
50 |
- |
- |
| 0 to 100 psig (0 to 6.89 barg) |
- |
- |
100 |
- |
- |
| 0 to 150 psig (0 to 10.34 barg) |
- |
- |
150 |
- |
- |
| 0 to 200 psig (0 to 13.79 barg) |
- |
- |
200 |
- |
- |
| 0 to 250 psig (0 to 17.24 barg) |
- |
- |
250 |
- |
- |
| 0 to 500 psig (0 to 34.47 barg) |
- |
- |
500 |
- |
- |
| 0 to 1000 psig (0 to 68.95 barg) |
- |
- |
1000 |
- |
- |
| Special scaling requests1 |
- |
- |
PXX |
- |
- |
| Temperature Sensor or Transmitter |
No pressure transmitter |
- |
- |
- |
XXXX |
- |
| Temperature without preamplifier (RTD only) Teflon® RTD internal wires - 40 to 400°F (- 40 to 204°C) |
- |
- |
- |
RTD-T |
- |
| Temperature without preamplifier (RTD only) fiberglass RTD internal wires 150 to 800°F (65 to 427°C)(Models 700 and 960 only) |
- |
- |
- |
RTD-F |
- |
| Temperature sensor with preamplifier scaled from 32 to 68 °F (liquid/gas) |
- |
- |
- |
T09 |
- |
| 0 to 250° F (liquid/gas) |
- |
- |
- |
T10 |
- |
| - 40 to 150°F (liquid/gas) |
- |
- |
- |
T11 |
- |
| 212 to 400°F (liquid/gas) |
- |
- |
- |
T12 |
- |
| 212 to 500°F (steam) (Model 700, 910, 960 only) |
- |
- |
- |
T14 |
- |
| - 17.7 to 121.1°C (liquid/gas) |
- |
- |
- |
T20 |
- |
| - 40 to 65°C (liquid/gas) |
- |
- |
- |
T21 |
- |
| 100 to 260°C (steam)(Model 700, 910, 960 only) |
- |
- |
- |
T24 |
- |
| Special scaling requests1 |
- |
- |
- |
TXX |
- |
| Electronics |
EZ-Logic™ with local rate and total2 |
- |
- |
- |
- |
LOC-TOT |
| Remote-mount electronics3 |
- |
- |
- |
- |
RMT |
| FM approved6 |
- |
- |
- |
- |
FM |
| CSA approved7 |
- |
- |
- |
- |
CSA |
| Integral 110 VAC input4,5 |
- |
- |
- |
- |
110 |
| Integral 220 VAC input4,5 |
- |
- |
- |
- |
220 |
V-Bar-910-2F900-200-T12-LOC-TOT represents a Model V-Bar-910 insertion vortex flowmeter for liquid, gas, or steam service with a 2" 900# flange, a pressure transmitter scaled to 0 to 200 psig (0 to 13.79 barg), a temperature sensor and transmitter scaled to 212 to 400°F, and EZ-Logic™ electronics.
Notes:
- Special transmitter scaling is available. Please note scaling range below Model code when ordering. If no special scaling is indicated, transmitter will be scaled per Model code.
- Unidirectional only. Unit has 4 to 20 mA and frequency output.
- The standard remote option comes with 30' of cable.
- Not available for use with pressure and temperature transmitters.
- Not available with European CE Mark.
- Certified by FM for Class I, Div. 2, Groups A, B, C, & D; Class II, III, Div. 2, Groups F & G; NEMA 4X. Not approved by FM when using a 4 to 20 mA temperature transmitter or a 110/220 VAC power supply option. If FM is required, use RTD option only for temperature selection.
- Certified by CSA for Class I, Div. 2, Groups A, B, C, & D; Class II, III, Div. 2, Groups F & G; Type 4X. Not approved by CSA when using a 4 to 20 mA temperature transmitter or a 110/220 VAC power supply option. If CSA is required, use RTD option only for temperature selection.
|
|